NUKEFACT #35

INVERSE MULTIPLICATION and FUEL LOADING

PART II - APPLICATION

last update May 25, 2001

In NUKEFACT 34, Inverse Multiplication and Fuel Loading - Part I: Fundamentals, the process of non-fission source multiplication was reviewed and inverse multiplication was defined. It was shown that 1/M was a linear function of keff. Unfortunately, actual fuel loading curves do not reflect this valuable linear relationship. However, all commercial reactors have now undergone a sufficient number of core loadings and refuelings so that reference curves from actual loadings are available as guides. Herein, we illustrate how inverse multiplication is currently applied and suggest possible improvements.

For purposes of simplicity, the examples employ only a few fuel assemblies. Typically, the number of fuel assemblies loaded into large commercial reactors range between 150 and 250 units. In BWRs each fuel assembly contains a fully inserted control rod, while PWRs use a combination of control rods and B-10 poison in the moderator. In both, when the loading is completed, the core is in a shutdown condition. Criticality is not attained during the fuel loading, in fact it is to be avoided. In each of the following examples, the final fuel assembly loading produces keff = 0.9000.

Loading Fuel Assemblies of Equal Worth

With inverse multiplication and fuel assembly worth defined we can now take a hypothetical fuel loading and generate a fuel loading 1/M diagram. Table 35.1 contains data for loading nine fuel cells of equal worth, i.e. where delta(delta-k) for each cell is identical at, delta(delta-k) = +0.1000. Note that per Equation 34.14 the keff value is obtained by adding the individual assembly worth to the previous keff value.

FUEL ASSEMLIES LOADED "i"
FUEL ASSEMBLY WORTH delta(delta-k)
kieffective
INVERSE MULTIPLICATION -kieff + 1
0-0.00001.0000
10.10000.10000.9000
20.10000.20000.8000
30.10000.30000.7000
40.10000.40000.6000
50.10000.50000.5000
60.10000.60000.4000
70.10000.70000.3000
80.10000.80000.2000
90.10000.90000.1000

TABLE 35.1 - FUEL LOADING with FUEL ASSEMBLIES of EQUAL WORTH

Column 1 lists the number of fuel assemblies loaded. Column 2 is the individual fuel assembly worth, delta(delta-k). Column 3 is the keff value after the fuel cell of Column 1 is loaded. Column 4 is the inverse multiplication value based on the value of keff, using Equation 34.5. Figure 35.1 is a graphical display of this data:


FIGURE 35.1 - 1/M versus keff (for assemblies of equal worth)

The vertical axis is inverse multiplication (1/M) and the horizontal axis is keff. Here we see that the ideal 1/M plot is a straight line with a slope of -1, a y-axis intercept of 1/M = 1.0, and a projected x-axis intercept of keff = 1.0.

The 1/M data are typically plotted versus the number of fuel assemblies (cells) loaded, as shown in Figure 35.2.


Figure 35.2 - 1/M versus Number of Assemblies Loaded (of Equal Worth)

The vertical axis is inverse multiplication and the horizontal axis is number of assemblies loaded. Again, the 1/M plot is a straight line with a negative slope. However, in this instance, the straight line is fortuitous ... and is not seen in practice because fuel assemblies are never of equal worth throughout the loading.

Loading Fuel Assemblies of Decreasing Worth

As a second example we proceed to a case more representative of an actual fuel loading. Table 35.2 contains data for loading seven fuel assemblies of unequal worth. Typically, the first assembly loaded contributes the largest worth, in this case delta(delta-k) = +0.3000. Thereafter, the worth of each assembly loaded gradually decreases. For this example the worth of the second assembly is +0.2000 and assemblies three through five are worth +0.1000 each. Assemblies six and seven are worth +0.0500 each.

FUEL ASSEMLIES LOADED "i"
FUEL ASSEMBLY WORTH delta(delta-k)kieffective

INVERSE MULTIPLICATION -kieff + 1
0-0.00001.0000
10.30000.30000.7000
20.20000.50000.5000
30.10000.60000.4000
40.10000.70000.3000
50.10000.80000.2000
60.05000.85000.1500
70.05000.90000.1000

TABLE 35.2 - FUEL LOADING with ASSEMBLIES of DECREASING WORTH

Column 1 lists the number of fuel assemblies loaded. Column 2 is the individual fuel assembly worth, delta(delta-k). Column 3 is the keff value after the fuel cell of Column 1 is loaded. Column 4 is the inverse multiplication value based on the value of keff, using Equation 34.5. Figure 35.3 is a graphical display of this data:


Figure 35.3 - 1/M versus keff (for assemblies of decreasing worth)

As before, we first set the vertical axis as inverse multiplication and the horizontal axis as keff. Here we see that, even though the individual data points are no longer evenly spaced in terms of keff, the 1/M plot remains as a straight line with a slope of -1, a y-axis intercept of 1/M = 1.0, and a projected x-axis intercept of keff = 1.0. Note that the initial horizontal spacing between 1/M points is large and as the worth of the assembly decreases the horizontal spacing also decreases. If the assemblies are of equal or decreasing worth, the distance the next assembly extends the loading line should not be greater that of the immediately preceding assembly. This provides a means for predicting the result of the next assembly to be loaded. When plotting 1/M versus number of assemblies loaded, the horizontal spacing between points remains constant.

Then, as by current convention, the 1/M data are plotted versus the number of fuel assemblies (cells) loaded, as shown in Figure 35.4.


Figure 35.4 - 1/M versus Number of Assemblies Loaded (of decreasing worth)

Suddenly, things do not appear quite so linear. The 1/M plot has a curvature that is concave to the axes, no longer being a straight line. And, why should it be? Equation 34.5 indicates the 1/M is a linear function of keff , not of the number of cells loaded. If the fuel assemblies are of unequal worth, as they always are in practice, conversion of the x-axis of the 1/M graphic from keff to number of assemblies loaded eliminates any linear relationship.

This form of loading curve is considered to be conservative because it initially projects criticality to occur with fewer assemblies than the intended full core loading. However, as the loading nears completion, the slope of the loading curve decreases and the projection to criticality becomes more realistic.

Loading Final Fuel Assemblies of Minimal Worth

As a continuation of the above example, suppose that two additional fuel assemblies are loaded which have very small worth. This too is representative of commercial reactor fuelings where the total number of assemblies is large. Table 35.3 contains data for loading two fuel assemblies of minimal worth, following the seven assemblies loaded in the previous example. The worth of the eighth and ninth assemblies loaded is +0.0010 for each.

FUEL ASSEMLIES LOADED "i"
FUEL ASSEMBLY WORTH delta(delta-k)
kieffective

INVERSE MULTIPLICATION -kieff + 1
0-0.00001.0000
10.30000.30000.7000
20.20000.50000.5000
30.10000.60000.4000
40.10000.70000.3000
50.10000.80000.2000
60.05000.85000.1500
70.05000.90000.1000
80.00100.90100.0990
90.00100.90200.0980

TABLE 35.3 - FUEL LOADING with FINAL ASSEMBLIES of MINIMAL WORTH

Column 1 lists the number of fuel assemblies loaded. Column 2 is the individual fuel assembly worth, delta(delta-k). Column 3 is the keff value after the fuel cell of Column 1 is loaded. Column 4 is the inverse multiplication value based on the value of keff, using Equation 34.5. For 1/M versus keff the loading curve still appears as shown in Figure 35.3, with the 1/M values for assemblies eight and nine overlaying the data point for the seventh assembly.

Figure 35.5 is a graphical display of this data versus number of assemblies loaded:


Figure 35.5 - IM versus Number of Assemblies Loaded (final assemblies of minimal worth)

Now, in addition to being notably non-linear, the 1/M plot flattens out as the worth of fuel assemblies added to a very large configuration contribute only small reduction in reactor subcritical delta-k. In this case, the loading curve projection for the final assemblies loaded indicates that an infinite number of assemblies are required to attain criticality. For large commercial reactors, the effect of each of these assemblies on core leakage is very minimal. The 1/M value is essentially a measure of kinfinity. Criticality will not be reached regardless of how many additional assemblies are loaded.

This example illustrates a loading curve shape that is representative of many, if not most, commercial refuelings. The fact that actual determination of 1/M must be based on Nuclear Instrument count data, as discussed in a future NUKEFACT, introduces statistical variations into the data points of Table 35.3, which results in a loading curve that is not so smooth as shown in this simple example. However, this does not alter the fact that the overall shape of the loading curve is determined by the diminishing worth of the successive fuel assemblies added to the configuration.

Loading Fuel Assemblies of Increasing Worth

As a final example to cover the remaining possibility, we proceed to a case that may be a hypothetical situation, or may occur under very unusual conditions. Table 35.4 contains data for loading seven fuel assemblies of unequal worth. The first two assemblies loaded contribute the least worth, in this case delta(delta-k) = +0.0500 for each assembly. Thereafter, the worth of each assembly loaded gradually increases. For this example the worth of the third through fifth assemblies is +0.1000 each. The worth of the sixth assembly is +0.2000 and the worth of the seventh assembly is +0.3000.

FUEL ASSEMLIES LOADED "i"
FUEL ASSEMBLY WORTH delta(delta-k)
kieffective

INVERSE MULTIPLICATION -kieff + 1
0-0.00001.0000
10.05000.05000.9500
20.05000.10000.9000
30.10000.20000.8000
40.10000.30000.7000
50.10000.40000.6000
60.20000.60000.4000
70.30000.90000.1000

TABLE 35.4 - FUEL LOADING with ASSEMBLIES of INCREASING WORTH

Column 1 lists the number of fuel assemblies loaded. Column 2 is the individual fuel assembly worth, delta(delta-k). Column 3 is the keff value after the fuel cell of Column 1 is loaded. Column 4 is the inverse multiplication value based on the value of keff, using Equation 34.5. Figure 35.6 is a graphical display of this data:


Figure 35.6 - IM versus keff (for assemblies of increasing worth)

As before, we first set the vertical axis as inverse multiplication and the horizontal axis as keff. And again, we see that, even though the individual data points are no longer evenly spaced in terms of keff, the 1/M plot remains as a straight line with a slope of -1, a y-axis intercept of 1/M = 1.0, and a projected x-axis intercept of keff = 1.0. Note that the initial horizontal spacing between 1/M points is small and as the worth of the assemblies increase, the horizontal spacing also increases. When plotting 1/M versus number of assemblies loaded, the horizontal spacing between points remains constant.

Then, as by current convention, the 1/M data are plotted versus the number of fuel assemblies (cells) loaded, as shown in Figure 35.7.


Figure 35.7 - IM versus Number of Assemblies Loaded (of increasing worth)

Here again, with cells of unequal worth, the loading curve deviates significantly from linear. The 1/M plot has a curvature that is convex to the axes, no longer being a straight line. The reason for this shape is the same as given in the second example, 1/M is only a linear function of keff and not of the number of cells loaded. If the fuel assemblies are of unequal worth, conversion of the x-axis of the 1/M graphic from keff to number of assemblies loaded eliminates any linear relationship.

This form of loading curve is considered to be non-conservative because it initially projects criticality to require many more assemblies than the intended full core loading. However, as the loading nears completion, the slope of the loading curve increases and the projection to criticality becomes more realistic.

SUMMARY

For the examples given the worth of fuel assemblies have been assumed to change in a particular manner. In practice, such change may vary. The worth of each assembly depends on the order in which it is loaded and its location in the core. It is possible that one assembly may be of less worth than the previous assembly, while the following assembly is worth more.

The potential benefit of the loading curve (1/M vs keff) is that it will provide an ongoing linear projection to the critical condition during the loading of fuel assemblies. Unfortunately, this promise is rarely realized because the operational loading curve plots 1/M versus the number of assemblies loaded. As a result, the criticality projections from the first few assemblies loaded are likely to be unreliable, either projecting far fewer or many more assemblies than required to attain criticality. Fortunately, even these loading curves tend toward improved projections as the loading nears completion.

It would seem that there is potential room for improvement in application of the loading curve to commercial reactor fuelings. Since 1/M is nothing more than the absolute value of the subcitical delta-k, k-effective is easily determined for creating a second loading curve, i.e. a linear loading curve that plots 1/M versus keff. It is quite likely that, with little extra effort, these two forms of the loading curve would allow more reliable interpretation of the proximity to criticality than the single conventional loading curve. The curve with 1/M versus keff always projects to the same end-point (keff = 1.0000).

The influence of instrument geometry will be addressed in a future NUKEFACT. Adverse instrument geometry can create non-linearities in the loading curve, of the same form as illustrated for assemblies of unequal worth.


HomePage | NukeFacts | ExamBank | PopQuiz | Visuals | NRC | Rx TRN | Xe TRN | FeedBack | E-mailXpress |